| The
G3B is a power gas burner for natural or propane gas - completely
assembled, using premix combustion and hot surface ignition
with flame rectification flame sensing. Converts from propane
to natural gas with just an orifice change - no conversion
kit needed. |
| |
|
|
|
Input
|
|
60,000
to 180,000 Btuh |
| |
|
|
|
Fuels
|
|
Natural
gas or Propane Gas |
| |
|
Maximum
Supply Pressure: 14 inches w.c.
|
| |
|
Minimum
Supply Pressure: 5.0 inches w.c. |
|
|
|
Manifold
Pressure: 3.5 inches w.c. |
| |
|
|
|
Electrical
|
|
Power:
120 vac/60Hz/1-Phase |
|
|
|
Current:
Approximately 8 amps |
|
|
|
Motor:
1/50 HP, 3250 RPM |
|
|
|
Gas
Valve Power: 24 vac/60 Hz |
|
|
|
|
|
Ignition
|
|
Norton
Hot Surface Ignitor, 120 vac
|
|
|
|
|
|
Control
|
|
Fenwal
Model 05-32 Primary Control
7 Sec. Trial for Ignition (TFI)
45 Sec. Pre-purge/ignitor warm-up
Recyle on Flame Failure
Factory installed and wired in control panel
Panel includes valve-on light, transformer & relay |
|
|
|
|
|
Orifice
Selection
|
|
|
| |
|
|
|
Agencies
|
|
CSA
Certified (US) |
|
|
|
|