Carlin Combustion
 
 
Features & Benefits
  Easy-wire terminal strip
    Microprocessor-operated (Processor coordinates operation and diagnostic)
    Easy remote sense (Electronic sensor, wired to control)
    Self-checking program (Control locks out on diagnostic failure)
    Diagnostic/status LED's (LED's indicate power, call for heat, and lockout)
    SMC Technology on burner relay (Safety Monitoring Circuit) Lockout when welded contact sensed
     
Model 90524A
  Triple Limit or Cold-start Control
The 90524 triple limit control provides high limit function and can also provide minimum water temperature control for operating with a tankless heater in a boiler. Function can be turned off by turning Low Limit setting to Off. Low temperature limit to prevent flow through boiler if temperature is below preset minimum for preventing condensation in conventional boilers. Operates as a col-start control when Low Limit is Off. Provides input from zone controller or relays and output to enable circulators. Provides operation of burner/gas valve and heating circulator.
Power Input
(L1-L2)
  120 vac, 10 VA, 60 Hz
Control Power
(T-T)
  24 vac, 130 mA
High Limit Range
 

Adjustable

High Limit Differential
  Fixed if low limit is used or if differential set point is Off. Adjustable if low limit is turned Off.
Low Limit Range
  Adjustable with Off position
Low Limit Differential
  Adjustable fixed if differential set point is Off.
Low Temp Function
  Fixed
Low Temp Differential
  Fixed
Temperature ranges Settings
  Any value/range between 50-250 degrees
Temperature ranges Differential
  Any value/range between 5-100 degrees
Contact Ratings Full Load
  Burner, circulator and ZC contacts 120 vac, 10 amps (total current on all contacts not to exceed 16 amps)
Contact Ratings Locked Rotor
  120 vac, 60 amps total current on all contacts not to exceed 96 amps
Ambient Temperature
  +32 to +140 Degrees
Storage Temperature
  -40 to +185 Degrees
     
Wiring Diagram
 
Agencies
  UL Listed US and Canada