Features
& Benefits
|
|
Multiple sensor option (3) (Using individual and/or dual sensor assemblies) |
| |
|
Sensor Redundancy (Higher temperature of two operating sensors used) |
| |
|
Easy remote sense (Electronic sensors wired to control) |
| |
|
Smart manual reset (Manual reset only if operating limit doesn't open) |
| |
|
Serviceman reset protection (Latch-up after three consecutive lockouts) Latch-up mode shuts down the control after three consecutive lockouts and requires a special procedure to reset. This ensures the owner will call in a licensed technician to troubleshoot and correct burner problems. |
| |
|
Power-independent lockout (Power cycling won't reset from lcokout or latch-up) |
| |
|
Diagnostic LED's (Power, call for heat, and lockout/latchup) |
| |
|
SMC Technology (Safety Monitoring Circuit) Provides two limit relays. Carlin's Safety Monitoring Circuit monitors the contacts for both relays. Lockout occures if a limit relay contact is found closed when it should be open.) |
| |
|
|
|
Model
90320B
|
|
Dual Limit Temperature Control
Operating and high limit action
Smart manual reset on high limit
Operating limit sensors, redundant
High limit sensor
Operating and limit contacts in series
|
|
Power
Input
(Red-White Wire)
|
|
240
vac, 50/60 Hz, 12 VA |
|
Contacts
|
|
2 in Series |
|
Contact
Rating
|
|
Motor Load: 240 vac, 50/60 Hz, 1 HP
General: 120/240 vac, 50/60 Hz, 15 Amps
|
|
Wires
|
|
Quantity:
3
240 vac Hot/Neutral: Red-white/White
Limits Out: Black |
|
Adjustable
Operating Limit Range
|
|
Any
range between 50°F to 240°F |
Fixed High Limit Temperature |
|
Any value from 160°F to 240°F |
|
Fixed
Differential (Subtractive)
|
|
Any
value from 5°F to 100°F |
|
Operating
Temperature Limits
|
|
+32°F
to +140°F |
|
Storage
Temperature Limits
|
|
-40°F
to +185°F |
|
Wiring
Diagram
|
|
|
|
Agencies
|
|
None |
| |
|
|