Features
& Benefits
|
|
Microprocessor-operated
(Processor coordinates limit and diagnostic functions) |
| |
|
Easy
Remote Sense (Electronic sensor, wired to control) |
| |
|
Select
from break-on-rise, make-on-rise or SPDT operation |
| |
|
Self-checking
Program (Control locks out on diagnostic failure) |
| |
|
Diagnostic
LED's (Power, Call for Heat, Lockout/latch-up) |
| |
|
|
|
Model
90200A
|
|
Temperature Limit Control
1 break-on-rise contact
1 electronic sensor
Lockout on diagnostic failure
Reset from lockout via power cycle |
|
Power
Input
(Red/White Wire)
|
|
120
vac, 11 VA |
|
Contacts
(Action on Temperature Rise)
|
|
1
Breaks |
|
Contact
Rating
|
|
Full
Load: 120 vac, 10 Amps
Locked Rotor: 120 vac, 60 Amps
|
|
Wires
|
|
Quantity:
3
120 vac Hot & Limit In/Neutral: Red-white/white
Break-on-Rise Out: Black
Make-on-Rise Out: NA |
|
Adjustable
Operating Limit Range
|
|
Any
range between 50°F to 240°F |
|
Fixed
High Limit Temperature
|
|
Any
value from 160°F to 240°F |
|
Fixed
Differential (Subtractive)
|
|
Any
value from 5°F to 100°F |
|
Operating
Temperature Limits
|
|
+32°F
to +140°F |
|
Storage
Temperature Limits
|
|
-40°F
to +185°F |
|
Wiring
Diagram
|
|
|
|
Agencies
|
|
UL
& ULC Listed or Recognized Component (US & Canada) |
| |
|
|
|
Model
90200B
|
|
Temperature Limit Control
1 Make-on-Rise Contact
1 Electronic Sensor
Lockout on Diagnostic Failure
Reset from lockout via power cycle |
|
Power
Input
(Red/White Wire)
|
|
120
vac, 11 VA |
|
Contacts
(Action on Temperature Rise)
|
|
1
Makes |
|
Contact
Rating
|
|
Full
Load: 120 vac, 10 Amps
Locked Rotor: 120 vac, 60 Amps
|
|
Wires
|
|
Quantity:
3
120 vac Hot & Limit In/Neutral: Red-white/white
Break-on-Rise Out: NA
Make-on-Rise Out: Black-white |
|
Adjustable
Operating Limit Range
|
|
Any
range between 50°F to 240°F |
|
Fixed
High Limit Temperature
|
|
Any
value from 160°F to 240°F |
|
Fixed
Differential (Subtractive)
|
|
Any
value from 5°F to 100°F |
|
Operating
Temperature Limits
|
|
+32°F
to +140°F |
|
Storage
Temperature Limits
|
|
-40°F
to +185°F |
|
Wiring
Diagram
|
|
|
|
Agencies
|
|
UL
& ULC Listed or Recognized Component (US & Canada) |
| |
|
|
|
Model
90100D
|
|
Temperature Limit Control
SPDT contacts (2 break-/1 make-on rise)
1 Electronic sensor
Lockout on diagnostic failure
Reset from lockout via power cycle |
|
Power
Input
(Red/White Wire)
|
|
120
vac, 11 VA |
|
Contacts
(Action on Temperature Rise)
|
|
1
Breaks, 1 Makes |
|
Contact
Rating
|
|
Full
Load: 120 vac, 10 Amps
Locked Rotor: 120 vac, 60 Amps
|
|
Wires
|
|
Quantity:
4
120 vac Hot & Limit In/Neutral: Red-white/white
Break-on-Rise Out: Black
Make-on-Rise Out: Black-white |
|
Adjustable
Operating Limit Range
|
|
Any
range between 50°F to 240°F |
|
Fixed
High Limit Temperature
|
|
Any
value from 160°F to 240°F |
|
Fixed
Differential (Subtractive)
|
|
Any
value from 5°F to 100°F |
|
Operating
Temperature Limits
|
|
+32°F
to +140°F |
|
Storage
Temperature Limits
|
|
-40°F
to +185°F |
|
Wiring
Diagram
|
|
|
|
Agencies
|
|
UL
& ULC Listed or Recognized Component (US & Canada) |