Features
& Benefits
|
|
Multiple
Sensor Option (2 or32) (Using individual and/or dual sensor
assemblies) |
| |
|
Sensor
Averaging (Average operating limit, high limit or both) |
| |
|
Easy
Remote Sense (Electronic sensors, wired to control) |
| |
|
Smart
Manual Reset (Manual reset only if operating limit doesn't
open) |
| |
|
Serviceman reset protection (Latch-up after three consecutive lockouts) Latch-up mode shuts down the control after three consecutive lockouts and requires a special procedure to reset. This ensures the owner will call in a licensed technician to troubleshoot and correct burner problems. |
| |
|
Power-independent
Lockout (Power cycling won't reset from lockout or latch-up) |
| |
|
Diagnostic
LED's (Power, Call for Heat, Lockout/latch-up) |
| |
|
SMC Technology (Safety Monitoring Circuit) Provides two limit relays. Carlin's Safety Monitoring Circuit monitors the contacts for both relays. Lockout occures if a limit relay contact is found closed when it should be open.) |
| |
|
|
|
Model
90100A
|
|
Dual
Limit Temperature Control
Operating and high limit action
Smart manual reset on high limit
2 sensors (electronically averaged)
1 contact - operating limit
1 contact - high limit |
|
Power
Input
(Red/White Wire)
|
|
120
vac, 11 VA |
|
Contacts
|
|
2
Independent |
|
Contact
Rating
|
|
Full
Load: 120 vac, 10 Amps
Locked Rotor: 120 vac, 60 Amps
|
|
Wires
|
|
Quantity:
6
120 vac Hot/Neutral: Red-white/white
Operating Limit In/Out: Black-green/black
High limit In/Out: Black-red/black-yellow |
|
Adjustable
Operating Limit Range
|
|
Any
range between 50°F to 240°F |
|
Fixed
High Limit Temperature
|
|
Any
value from 160°F to 240°F |
|
Fixed
Differential (Subtractive)
|
|
Any
value from 5°F to 100°F |
|
Operating
Temperature Limits
|
|
+32°F
to +140°F |
|
Storage
Temperature Limits
|
|
-40°F
to +185°F |
|
Wiring
Diagram
|
|
|
|
Agencies
|
|
UL
& ULC Listed or Recognized Component (US & Canada) |
| |
|
|
|
Model
90100B
|
|
Dual
Limit Temperature Control
Operating and high limit action
Smart manual reset on high limit
2 operating limit sensors, averaging
1 high limit sensor
1 contact - operating limit
1 contact - high limit |
|
Power
Input
(Red/White Wire)
|
|
120
vac, 11 VA |
|
Contacts
|
|
2
Independent |
|
Contact
Rating
|
|
Full
Load: 120 vac, 10 Amps
Locked Rotor: 120 vac, 60 Amps
|
|
Wires
|
|
Quantity:
6
120 vac Hot/Neutral: Red-white/white
Operating Limit In/Out: Black-green/black
High limit In/Out: Black-red/black-yellow |
|
Adjustable
Operating Limit Range
|
|
Any
range between 50°F to 240°F |
|
Fixed
High Limit Temperature
|
|
Any
value from 160°F to 240°F |
|
Fixed
Differential (Subtractive)
|
|
Any
value from 5°F to 100°F |
|
Operating
Temperature Limits
|
|
+32°F
to +140°F |
|
Storage
Temperature Limits
|
|
-40°F
to +185°F |
|
Wiring
Diagram
|
|
|
|
Agencies
|
|
UL
& ULC Listed or Recognized Component (US & Canada) |
| |
|
|
|
Model
90100C
|
|
Dual
Limit Temperature Control
Operating and high limit action
Smart manual reset on high limit
1 operating limit sensor
2 high limit sensors, averaged
1 contact - operating limit
1 contact - high limit |
|
Power
Input
(Red/White Wire)
|
|
120
vac, 11 VA |
|
Contacts
|
|
2
Independent |
|
Contact
Rating
|
|
Full
Load: 120 vac, 10 Amps
Locked Rotor: 120 vac, 60 Amps
|
|
Wires
|
|
Quantity:
6
120 vac Hot/Neutral: Red-white/white
Operating Limit In/Out: Black-green/black
High limit In/Out: Black-red/black-yellow |
|
Adjustable
Operating Limit Range
|
|
Any
range between 50°F to 240°F |
|
Fixed
High Limit Temperature
|
|
Any
value from 160°F to 240°F |
|
Fixed
Differential (Subtractive)
|
|
Any
value from 5°F to 100°F |
|
Operating
Temperature Limits
|
|
+32°F
to +140°F |
|
Storage
Temperature Limits
|
|
-40°F
to +185°F |
|
Wiring
Diagram
|
|
|
|
Agencies
|
|
UL
& ULC Listed or Recognized Component (US & Canada) |