Features
& Benefits
|
|
Multiple
Sensor Option (1 or 2) (Using individual and/or dual sensor
assemblies) |
| |
|
Easy
Remote Sense (Electronic sensors, wired to control) |
| |
|
Smart
Manual Reset (Manual reset only if operating limit doesn't
open) |
| |
|
Serviceman reset protection (Latch-up after three consecutive lockouts) Latch-up mode shuts down the control after three consecutive lockouts and requires a special procedure to reset. This ensures the owner will call in a licensed technician to troubleshoot and correct burner problems. |
| |
|
Power-independent
Lockout (Power cycling won't reset from lockout or latch-up) |
| |
|
Diagnostic
LED's (Power, Call for Heat, Lockout/latch-up) |
| |
|
SMC Technology (Safety Monitoring Circuit) Provides two limit relays. Carlin's Safety Monitoring Circuit monitors the contacts for both relays. Lockout occures if a limit relay contact is found closed when it should be open.) |
| |
|
|
|
Model
90000A
|
|
Dual
Limit Temperature Control
Operating and high limit action
Smart manual reset on high limit
2 sensors (operating and high limit)
1 contact - operating limit
1 contact - high limit |
|
Power
Input
(Red/White Wire)
|
|
120
vac, 11 VA |
|
Contacts
|
|
2
Independent |
|
Contact
Rating
|
|
Full
Load: 120 vac, 10 Amps
Locked Rotor: 120 vac, 60 Amps
|
|
Wires
|
|
Quantity:
6
120 vac Hot/Neutral: Red-white/white
Operating Limit In/Out: Black-green/black
High limit In/Out: Black-red/black-yellow
Limits Out: NA |
|
Adjustable
Operating Limit Range
|
|
Any
range between 50°F to 240°F |
|
Fixed
High Limit Temperature
|
|
Any
value from 160°F to 240°F |
|
Fixed
Differential (Subtractive)
|
|
Any
value from 5°F to 100°F |
|
Operating
Temperature Limits
|
|
+32°F
to +140°F |
|
Storage
Temperature Limits
|
|
-40°F
to +185°F |
|
Wiring
Diagram
|
|
|
|
Agencies
|
|
UL
& ULC Listed or Recognized Component (US & Canada) |
| |
|
|
|
Model
90000B
|
|
Redundant
Limit Temperature Control
Operating and high limit action
Smart manual reset on high limit
1 sensor
Operating and limit contacts in series |
|
Power
Input
(Red/White Wire)
|
|
120
vac, 11 VA |
|
Contacts
|
|
2
In Series |
|
Contact
Rating
|
|
Full
Load: 120 vac, 10 Amps
Locked Rotor: 120 vac, 60 Amps
|
|
Wires
|
|
Quantity:
3
120 vac Hot/Neutral: Red-white/white
Operating Limit In/Out: NA
High limit In/Out: NA
Limits Out: Black |
|
Adjustable
Operating Limit Range
|
|
Any
range between 50°F to 240°F |
|
Fixed
High Limit Temperature
|
|
Any
value from 160°F to 240°F |
|
Fixed
Differential (Subtractive)
|
|
Any
value from 5°F to 100°F |
|
Operating
Temperature Limits
|
|
+32°F
to +140°F |
|
Storage
Temperature Limits
|
|
-40°F
to +185°F |
|
Wiring
Diagram
|
|
|
|
Agencies
|
|
UL
& ULC Listed or Recognized Component (US & Canada) |
| |
|
|
Model 90000C |
|
Redundant Limit Temperature Control
Operating and high limit action
Smart manual reset on high limit
2 sensors (Operating and high limit)
Operating and limit contacts in series |
Power Input
(Red-White Wire) |
|
120 vac, 11 VA |
Contacts |
|
2 In Series |
Contact Rating |
|
Full Load: 120 vac, 10 Amps
Locked Rotor: 120 vac, 60 Amps |
Wires |
|
Quantity: 3
120 vac Hot/Neutral: Red-white/white
Operating Limit In/Out: NA
High limit In/Out: NA
Limits Out: Black |
Adjustable Operating Limit Range |
|
Any range between 50°F to 240°F |
Fixed High Limit Temperature |
|
Any value from 160°F to 240°F |
Fixed Differential (Subtractive) |
|
Any value from 5°F to 100°F |
Operating Temperature Limits |
|
+32°F to +140°F |
Storage Temperature Limits |
|
-40°F to +185°F |
Wiring Diagram |
|
|
Agencies |
|
UL & ULC Listed or Recognized Component (US & Canada) |