Carlin Combustion
 
 
Features & Benefits
  Multiple Sensor Option (1 or 2) (Using individual and/or dual sensor assemblies)
    Easy Remote Sense (Electronic sensors, wired to control)
    Smart Manual Reset (Manual reset only if operating limit doesn't open)
    Serviceman reset protection (Latch-up after three consecutive lockouts) Latch-up mode shuts down the control after three consecutive lockouts and requires a special procedure to reset. This ensures the owner will call in a licensed technician to troubleshoot and correct burner problems.
    Power-independent Lockout (Power cycling won't reset from lockout or latch-up)
    Diagnostic LED's (Power, Call for Heat, Lockout/latch-up)
    SMC Technology (Safety Monitoring Circuit) Provides two limit relays. Carlin's Safety Monitoring Circuit monitors the contacts for both relays. Lockout occures if a limit relay contact is found closed when it should be open.)
     
Model 90000A
  Dual Limit Temperature Control
Operating and high limit action
Smart manual reset on high limit
2 sensors (operating and high limit)
1 contact - operating limit
1 contact - high limit
Power Input
(Red/White Wire)
  120 vac, 11 VA
Contacts
  2 Independent
Contact Rating
 

Full Load: 120 vac, 10 Amps
Locked Rotor: 120 vac, 60 Amps

Wires
  Quantity: 6
120 vac Hot/Neutral: Red-white/white
Operating Limit In/Out: Black-green/black
High limit In/Out: Black-red/black-yellow
Limits Out: NA
Adjustable Operating Limit Range
  Any range between 50°F to 240°F
Fixed High Limit Temperature
  Any value from 160°F to 240°F
Fixed Differential (Subtractive)
  Any value from 5°F to 100°F
Operating Temperature Limits
  +32°F to +140°F
Storage Temperature Limits
  -40°F to +185°F
Wiring Diagram
 
Agencies
  UL & ULC Listed or Recognized Component (US & Canada)
     
Model 90000B
  Redundant Limit Temperature Control
Operating and high limit action
Smart manual reset on high limit
1 sensor
Operating and limit contacts in series
Power Input
(Red/White Wire)
  120 vac, 11 VA
Contacts
  2 In Series
Contact Rating
 

Full Load: 120 vac, 10 Amps
Locked Rotor: 120 vac, 60 Amps

Wires
  Quantity: 3
120 vac Hot/Neutral: Red-white/white
Operating Limit In/Out: NA
High limit In/Out: NA
Limits Out: Black
Adjustable Operating Limit Range
  Any range between 50°F to 240°F
Fixed High Limit Temperature
  Any value from 160°F to 240°F
Fixed Differential (Subtractive)
  Any value from 5°F to 100°F
Operating Temperature Limits
  +32°F to +140°F
Storage Temperature Limits
  -40°F to +185°F
Wiring Diagram
 
Agencies
  UL & ULC Listed or Recognized Component (US & Canada)
     
Model 90000C
  Redundant Limit Temperature Control
Operating and high limit action
Smart manual reset on high limit
2 sensors (Operating and high limit)
Operating and limit contacts in series
Power Input
(Red-White Wire)
  120 vac, 11 VA
Contacts
  2 In Series
Contact Rating
 

Full Load: 120 vac, 10 Amps
Locked Rotor: 120 vac, 60 Amps

Wires
  Quantity: 3
120 vac Hot/Neutral: Red-white/white
Operating Limit In/Out: NA
High limit In/Out: NA
Limits Out: Black
Adjustable Operating Limit Range
  Any range between 50°F to 240°F
Fixed High Limit Temperature
  Any value from 160°F to 240°F
Fixed Differential (Subtractive)
  Any value from 5°F to 100°F
Operating Temperature Limits
  +32°F to +140°F
Storage Temperature Limits
  -40°F to +185°F