Carlin Combustion
 
 
Features & Benefits
  Flame Quality Monitoring (With automatic modum calling for service - reduces major servicing with longer service intervals
    Accurate Fuel Tank Monitoring (With automatic modem calling for delivery - no runouts; fewer deliveries
    Autodialing (Calls automatically to report operation status for fuel delivery and emergency or periodic service notification (daily)
    PC Software Interface (Includes trend-indication graphics of monitored performance parameters - future upgrades will include software interface to dealer accounting software
    Interrupted Duty Ignition
    Recycle on Flame Failure
    Serviceman Reset Protection (Latch-up after three consecutive lockouts)
    Diagnostic LED's
    Valve Delay on/motor Delay Off (Pre/post Purge - Contact Carlin for Available timings)
    15 Second Trial for Ignition (TFI) Other Timings Available
    1.3 Second Flame Failure response time (FFRT)
    Alarm Contacts
    Thermostat/aquastat Compatible
    SMC (Safety Monitoring Circuit) Technology
     
Power Input
(Red/White Wire)
  120 vac, 60 Hz, 9 VA
Limit Circuit Input
(Black Wire)
  120 vac, 60 Hz
Motor Load
  120 vac, 60 Hz, 10 FLA, 60 LRA
Ignitor Load
  120 vac, 60 Hz, 500 VA
Valve Load
  120 vac, 60 Hz, 2.0 Amps
Alarm Contacts
  24 V, AC/DC, 2 Amps
Operating Temperature Limits
 

0°F to + 140°F

Storage Temperature Limits
  -40°F to +185°F
Stack Temperature Range
  70°F to 750°F (0°F to 680°F Net)
Humidity Range (Operating)
  0 to 95% RH, Noncondensing
UV Cell Resistance (Flame)
  <5 Megohms
Thermostat Anticipator Current
  0.2 Amp, AC
Cad Cell Resistance with Flame
  R < 1500 OHMS
Agencies
  TBA