Carlin Combustion
The 701CRD and 801CRD advanced oil burners feature Carlin's adjustable combustion head assembly - for unmatched fuel/air mixing, smooth light-offs and quiet running. The automatically-closed air damper and low-high-low step modulation (approximately 2:1 turndown) improve efficiency by closer matching of output to demand and reduced stand-by losses - typically savings of 15-20% in seasonal fuel usage when compared to single-stage flame retention burners. Proven for years in the field and in extensive boiler and furnace testing, these burners will meet your needs for commercial oil-burning applications.
     
Input
  701CRD: High Fire: 6.0 to 13.2 GPH, Low Fire: 3.6 to 6.6 GPH
    801CRD: High Fire: 11.4 to 19.8 GPH, Low Fire: 6.6 to 8.4 GPH
 
Fuels
  U.S. - No. 1 or No. 2 Fuel Oil
  Canada - No. 1 Oil or No. 2 Furnace Oil
 

Nozzles

(1) Low Fire Nozzle, (1) High Fire Nozzle, pattern and angle vary with application
Fuel Unit
2-Stage, "B" Style, 150 PSIG
Oil Valves
(2) Oil solenoid valves
     
Control
  Carlin 60200 Primary Control
     
Electrical
  Power: 120 vac/60Hz/1-Phase
  Limit Circuit Input (60200 Primary): 120 vac/60 Hz
    Control Circuit Load: 120 vac, 1.2 amps
 

Motor:
701CRD: 1/2 HP, 3450 RPM, 115/208-230 vac, 60 Hz, 1 phase, 8.4/3.8-4.2 amps
801CRD: 3/4 HP, 3450 RPM, 60 Hz, 115/208-230 vac, 60 Hz, 1 phase, 9.8/4.8-4.9 amps. Optional 208-230/460 vac, 60 Hz, 3 phase, 3.0-3.2/1/6 amps

    Motor Frame:
701CRD:
48-Frame, "N" Flange
801CRD: 56C-Frame
  Oil Valve Power: 120 vac/60 Hz
    Damper Motor (With End Switch): Honeywell M436A
 
Ignition
 

Carlin Model 41000 solid state electronic ignition

  Ignition Voltage: 14,000 volts
 
Agencies
  UL Listed: US & Canada