Carlin Combustion
 
 
Features & Benefits
  Interrupted Duty Ignition
    Recycle on Flame Failure
    Serviceman Reset Protection ( Latch-up after three consecutive lockouts)
    Diagnostic LED's
    Valve Delay on/motor Delay Off (Pre/Post Purge - Contact Carlin for Available Timings)
    15 Second Trial for Ignition (TFI) Other Timings Available
    1.3 Second Flame Failure response time (FFRT)
    Alarm Contacts
    Thermostat/aquastat Compatible
    SMC (Safety Monitoring Circuit) Technology
    European Configuration Available
     
Power Input
(Red/White Wire)
  208-240 vac, 50/60 Hz, 9 VA
Limit Circuit Input
(Black Wire)
  208-240 vac, 50/60 Hz
Motor Load
  5 FLA, 30 LRA
Ignitor Load
  208-240 vac, 50/60 Hz, 500 VA
Valve Load
  208-240 vac, 50/60 Hz, 0.3 Amps
Alarm Contacts
  24 V, AC/DC, 2 Amps
Operating Temperature Limits
 

+ 32°F to + 132°F

Storage Temperature Limits
  -40°F to +185°F
Thermostat Anticipator Current
  0.2 Amp, AC
Cad Cell Resistance with Flame
  R < 1500 OHMS
Wiring Diagram
 
Agencies
  NA