Carlin Combustion
 
 
Features & Benefits
  Interrupted Duty Ignition
    Recycle on Flame Failure
    Serviceman Reset Protection ( Latch-up after three consecutive lockouts)
    Diagnostic LED's
    15 Second Trial for Ignition (TFI) Other Timings Available
    1.3 Second Flame Failure response time (FFRT)
    Alarm Contacts
    Thermostat/aquastat Compatible
    SMC (Safety Monitoring Circuit) Technology
     
Power Input
(From Limit Circuit)
  120 vac, 60 Hz, 9 VA
Motor Load
  10 FLA/60 LRA
Ignitor Load
  120 vac, 60 Hz, 500 VA
Alarm Contacts
  24 V, AC/DC, 2 A
Operating Temperature Limits
 

+ 32°F to + 140°F

Storage Temperature Limits
  -40°F to +185°F
Thermostat Anticipator Current
  0.2 A, AC
Cad Cell Resistance with Flame
  R < 1500 OHMS
Wiring Diagram
 
Agencies
  UL & ULC Recognized Component United States & Canada